(read/write)


This property sets/gets the Voltage Limit for bus to which the regulated winding is connected (e.g. first customer). Default is 0.0. Set to a value greater then zero to activate this function.


Example


% Create DSS object

DSSObject = actxserver('OpenDSSEngine.DSS')

if ~DSSObject.Start(0),

                    disp('Unable to start openDSS');

                    return

end;

DSSText = DSSObject.Text;

DSSCircuit = DSSObject.ActiveCircuit;

% Compile a model        

DSSText.Command = 'Compile C:\myPath\myModel.dss';

DSSRegCtrls = DSSCircuit.RegControls;

% Activates the first RegControl of the list

i = DSSRegCtrls.First;

% verifies if the voltage limit functionality is ON for the active RegControl

myXfmr = DSSRegCtrls.VoltageLimit;

if DSSRegCtrls.VoltageLimit > 0,

                    disp('Voltage limit functionality ON');

end;