The following are the properties associated to the relay object:


Property

Description

(1) MonitoredObj

Full object name of the circuit element, typically a line, transformer, load, or generator, to which the relay's PT and/or CT are connected. This is the

"monitored" element. There is no default; must be specified.

(2) MonitoredTerm

Number of the terminal of the circuit element to which the Relay is connected. 1 or 2, typically. Default is 1.

(3) SwitchedObj

Name of circuit element switch that the Relay controls. Specify the full object name.Defaults to the same as the Monitored element. This is the "controlled" element.

(4) SwitchedTerm

Number of the terminal of the controlled element in which the switch is

controlled by the Relay. 1 or 2, typically. Default is 1.

(5) type

One of a legal relay type:


Current

Voltage

ReversePower

46 (neg seq current)

47 (neg seq voltage)

Generic (generic over/under relay)


Default is overcurrent relay (Current) Specify the curve and pickup settings

appropriate for each type. Generic relays monitor PC Element Control variables and trip on out of over/under range in definite time

(6) Phasecurve

Name of the TCC Curve object that determines the phase trip. Must have been previously defined as a TCC_Curve object. Default is none (ignored). For overcurrent relay, multiplying the current values in the curve by the "phasetrip" value gives the actual current.

(7) Groundcurve

Name of the TCC Curve object that determines the ground trip. Must have

been previously defined as a TCC_Curve object. Default is none (ignored).For overcurrent relay, multiplying the current values in the curve by the "groundtrip" valuw gives the actual current.

(8) PhaseTrip

Multiplier or actual phase amps for the phase TCC curve. Defaults to 1.0.

(9) GroundTrip

Multiplier or actual ground amps (3I0) for the ground TCC curve. Defaults to 1.0.

(10) TDPhase

Time dial for Phase trip curve. Multiplier on time axis of specified curve.

Default=1.0.

(11) TDGround

Time dial for Ground trip curve. Multiplier on time axis of specified curve.

Default=1.0.

(12) PhaseInst

Actual amps (Current relay) or kW (reverse power relay) for instantaneous

phase trip which is assumed to happen in 0.01 sec + Delay Time. Default is 0.0, which signifies no inst trip. Use this value for specifying the Reverse Power threshold (kW) for reverse power relays.

(13) GroundInst

Actual amps for instantaneous ground trip which is assumed to happen in 0.01 sec + Delay Time.Default is 0.0, which signifies no inst trip.

(14) Reset

Reset time in sec for relay. Default is 15. If

(15) Shots

Number of shots to lockout. Default is 4. This is one more than the number of reclose intervals.

(16) RecloseIntervals

Array of reclose intervals. If none, specify "NONE". Default for overcurrent relay is (0.5, 2.0, 2.0) seconds. Default for a voltage relay is (5.0). In a voltage relay, this is seconds after restoration of voltage that the reclose occurs. Reverse power relay is one shot to lockout, so this is ignored. A locked out relay must be closed manually (set action=close).

(17) Delay

Trip time delay (sec) for definite time relays. Default is 0.0 for current and

voltage relays. If >0 then this value is used instead of curves. Used exclusivelyby RevPower, 46 and 47 relays at this release. Defaults to 0.1 s for these relays.

(18) Overvoltcurve

TCC Curve object to use for overvoltage relay. Curve is assumed to be defined with per unit voltage values. Voltage base should be defined for the relay. Default is none (ignored).

(19) Undervoltcurve

TCC Curve object to use for undervoltage relay. Curve is assumed to be defined with per unit voltage values. Voltage base should be defined for the relay. Default is none (ignored).

(20) kvbase

Voltage base (kV) for the relay. Specify line‐line for 3 phase devices); lineneutral for 1‐phase devices. Relay assumes the number of phases of the monitored element. Default is 0.0, which results in assuming the voltage values in the "TCC" curve are specified in actual line‐to‐neutral volts.

(21) 47%Pickup

Percent voltage pickup for 47 relay (Neg seq voltage). Default is 2. Specify also base voltage (kvbase) and delay time value.

(22) 46BaseAmps

Base current, Amps, for 46 relay (neg seq current). Used for establishing pickup and per unit I‐squared‐t.

(23) 46%Pickup

Percent pickup current for 46 relay (neg seq current). Default is 20.0. When current exceeds this value * BaseAmps, I‐squared‐t calc starts.

(24) 46isqt

Negative Sequence I‐squared‐t trip value for 46 relay (neg seq current). Default is 1 (trips in 1 sec for 1 per unit neg seq current). Should be 1 to 99.

(25) Variable

Name of variable in PC Elements being monitored. Only applies to Generic

relay.

(26) overtrip

Trip setting (high value) for Generic relay variable. Relay trips in definite time if

value of variable exceeds this value.

(27) undertrip

Trip setting (low value) for Generic relay variable. Relay trips in definite time if

value of variable is less than this value.

(28) Breakertime

Fixed delay time (sec) added to relay time. Default is 0.0. Designed to represent

breaker time or some other delay after a trip decision is made.Use Delay_Time

property for setting a fixed trip time delay.Added to trip time of current and

voltage relays. Could use in combination with inst trip value to obtain a definite

time overcurrent relay.

(29) action

{Trip/Open | Close} Action that overrides the relay control. Simulates manual

control on breaker. "Trip" or "Open" causes the controlled element to open and

lock out. "Close" causes the controlled element to close and the relay to reset

to its first operation.

(30) basefreq

Base Frequency for ratings.

(31) enabled

{Yes|No or True|False} Indicates whether this element is enabled.