Properties
The properties, in numerical order, are:
|
Property |
Description |
|
bus1 |
Name of bus to which the generator is connected. Include node definitions if the terminal conductors are connected unusually. 3-phase Wye-connected generators have 4 conductors; Delta-connected have 3. Wye-connected generators, in general, have one more conductor than phases. 1-phase Delta has 2 conductors; 2-phase has 3. The remaining Delta, or line-line, connections have the same number of conductors as phases. |
|
Phases |
No. of phases this generator. |
|
Kv |
Base voltage for generator. For 2- or 3-phase generators, specified in phase-to-phase kV. For all other generators, the actual kV across the generator branch. If wye (star) connected, specify the phase-to-neutral (L-N) kV. If delta or phase-to-phase connected, specify the phase-to-phase (L-L) kV. |
|
Kw |
nominal kW for generator. Total of all phases. |
|
Pf |
nominal Power Factor for generator. Negative PF is leading (absorbing vars). Specify either PF or kvar (see below). If both are specified, the last one specified takes precedence. |
|
Model |
Integer defining how the generator will vary with voltage. Presently defined models are: 1: Generator injects a constant kW at specified power factor. 2: Generator is modeled as a constant admittance. 4: Const kW, Fixed Q (Q never varies) 5: Const kW, Fixed Q(as a constant reactance) 6: Compute load injection from User-written Model.(see usage of Xd, Xdp) 7: Constant kW, kvar, but current is limited when voltage is below Vminpu |
|
Yearly |
Name of Yearly load shape. |
|
Daily |
Name of Daily load shape. |
|
Duty |
name of Duty cycle load shape. Defaults to Daily load shape if not defined. |
|
Dispvalue |
Dispatch value. If = 0.0 then Generator follows dispatch curves. If > 0 then Generator is ON only when the global load multiplier exceeds this value. Then the generatorfollows dispatch curves (see also Status) |
|
Conn |
{wye | y | LN} for Wye (Line-Neutral) connection; {delta | LL} for Delta (Line-Line) connection. Default = wye. |
|
Kvar |
Base kvar. If this is specified, will supercede PF. (see PF) |
|
Rneut |
Neutral resistance ohms. If entered as negative, non-zero number, neutral is assumed open, or ungrounded. Ignored for delta or line-line connected generators. Default is 0. |
|
Xneut |
Neutral reactance, ohms. Ignored for delta or line-line connected generators. Assumed to be in series with Rneut value. |
|
Status |
{fixed | variable}. If Fixed, then dispatch multipliers do not apply. The generator is always at full power when it is ON. Default is Variable (follows curves). |
|
Class |
Integer number segregating the generator according to a particular user-defined class. Can be any number. |
|
Maxkvar |
Maximum kvar limit for Model = 3. Defaults to twice the specified load kvar. Always reset this if you change PF or kvar properties. |
|
Minkvar |
Minimum kvar limit for Model = 3. Enter a negative number if generator can absorb vars. Defaults to negative of Maxkvar. Always reset this if you change PF or kvar properties. |
|
Pvfactor |
Convergence deceleration factor for P-V generator model (Model=3). Default is 0.1. If the circuit converges easily, you may want to use a higher number such as 1.0. Use a lower number if solution diverges. Use Debugtrace=yes to create a file that will trace the convergence of a generator model. |
|
Debugtrace |
{Yes | No } Default is no. Turn this on to capture the progress of the generator model for each iteration. Creates a separate file for each generator named "GEN_name.CSV". |
|
Vminpu |
Default = 0.95. Minimum per unit voltage for which the Model is assumed to apply. Below this value, the generator model reverts to a constant impedance model. For Model 7, this is used to determine the upper current limit. For example, if Vminpu is 0.90 then the current limit is (1/0.90) = 111%. |
|
Vmaxpu |
Default = 1.05. Maximum per unit voltage for which the Model is assumed to apply. |
|
ForceON |
{Yes | No} Forces generator ON despite requirements of other dispatch modes. Stays ON until this property is set to NO, or an internal algorithm cancels the forced ON state. |
|
kVA |
kVA rating of electrical machine. Defaults to 1.2* kW if not specified. Applied to machine or inverter definition for Dynamics mode solutions. |
|
MVA |
MVA rating of electrical machine. Alternative to using kVA=. |
|
Xd |
Per unit synchronous reactance of machine. Presently used only for Thevenin impedance for power flow calcs of user models (model=6). Typically use a value from 0.4 to 1.0. Default is 1.0 |
|
Xdp |
Per unit transient reactance of the machine. Used for Dynamics mode and Fault studies. Default is 0.27.For user models, this value is used for the Thevenin/Norton impedance for Dynamics Mode. |
|
Xdpp |
Per unit subtransient reactance of the machine. Used for Harmonics. Default is 0.20. |
|
H |
Per unit mass constant of the machine. MW-sec/MVA. Default is 1.0. |
|
D |
Damping constant. Usual range is 0 to 4. Default is 1.0. Adjust to get damping |
|
UserModel |
Name of DLL containing user-written model, which computes the terminal currents for Dynamics studies, overriding the default model. Set to "none" to negate previous setting. |
|
UserData |
String (in quotes or parentheses) that gets passed to user-written model for defining the data required for that model. |
|
ShaftModel |
Name of user-written DLL containing a Shaft model, which models the prime mover and determines the power on the shaft for Dynamics studies. Models additional mass elements other than the single-mass model in the DSS default model. Set to "none" to negate previous setting. |
|
ShaftData |
String (in quotes or parentheses) that gets passed to user-written shaft dynamic model for defining the data for that model. |
|
DutyStart |
Starting time offset [hours] into the duty cycle shape for this generator, defaults to 0. |
|
Balanced |
{Yes | No*} Default is No. For Model=7, force balanced current only for 3-phase generators. Force zero- and negative-sequence to zero. |
|
XRdp |
Default is 20. X/R ratio for Xdp property for FaultStudy and Dynamic modes. Required to match published textbook fault study cases that have generators with both R and X specified. |
Inherited Properties
|
spectrum |
Name of harmonic voltage or current spectrum for this generator. Voltage behind Xd" for machine - default. Current injection for inverter. Default value is "default", which is defined when the DSS starts. |
|
Basefreq |
Base frequency for which this generator is defined. Default is 60.0 |
|
Like |
Name of another Generator object on which to base this one |